<?xml version="1.0" encoding="utf-8"?>
<Spec id="71" path="\5\6\5615fd027ec36dfbd319991e696dab1e.pdf"><Text id="13706" page="9">3.18 Cooling Water Piping: Seller shall provide single Buyerinterface connections for cooling water supply and return. Seller is responsible for distributing cooling water to and from the seal coolers, lube oil cooler, and jacket cooling (if applicable). Flexible piping may be used for ease of fitting and to avoid imposing additional stresses on pump components. Piping with valves shall be assembled in the factory as completely as possible on the pumpbaseplate.</Text><Text id="13719" page="1">l. SCOPE: This specification is for the design, fabrication, supply and delivery of fourteen (14) Boiler Feedwater Pump (BFP) packages as detailed in the Boiler Feedwater Pump Datasheet (DS). Each pump shall provide feedwater at two (2) different pressure levels to a multi-pressure Heat Recovery Steam Generator (HRSG). Each set of pumps will consist of a 2x100% pair where each pumpis independently designed to deliver the requisite conditions for full duct-fired operation and non-duct-fired operation. The boiler feed pumpsshall take suction from the LP Drum. Each pumpshall have aninter-stage take-off to provide feedwater to the IP economizer.</Text><Text id="13720" page="1">1.1 The Equipment offered shall be consistent with the best principles and practices of BFP design. Pumps shall be horizontal multi-stage centrifugal type. This specification provides the required details of performance and design. The pumpsshall be identical in all respects, and parts shall be interchangeable.</Text><Text id="13740" page="2">2.5.1 Runout Flow: The pumpshall be hydraulically capable of runout flows of 120% of either the curve-defining operating point, or the maximum flow case as defined in the DS, whicheveris greater. For variable speed pumps, the runout flow capability shall be tested at the pumpspeedthat delivers the flow and head specified for the speed-defining case ofthose listed in the DS. Seller shall represent this additional runout hydraulic capability as a dashed continuation of the pump performancecurve.</Text><Text id="13745" page="3">2.7 Efficiency: The maximumefficiency point (BEP) for each pump shall occur near the guaranteed pump capacity point. For variable speed pumps, the Seller shall provide performance curves for each operating Case in the DS, both with the proposal and as a formal submittal.</Text><Text id="13813" page="8">3.17 Coupling: Seller shall provide an all metal, flexible disk or diaphragm, non-lubricated spacer type coupling to suit operating speed, horsepower, and service requirements with a service factor of no less than 1.5 times the maximum torque. The flexible coupling, mounted on a cylindrical pump shaft extension, shall facilitate removal of the inboard bearinghousing assembly and cartridge mounted seal assembly for easy maintenance. Exposed coupling</Text><Text id="14025" page="1">l. SCOPE: This specification is for the design, fabrication, supply and delivery of fourteen (14) Boiler Feedwater Pump (BFP) packages as detailed in the Boiler Feedwater Pump Datasheet (DS). Each pump shall provide feedwater at two (2) different pressure levels to a multi-pressure Heat Recovery Steam Generator (HRSG). Each set of pumps will consist of a 2x100% pair where each pumpis independently designed to deliver the requisite conditions for full duct-fired operation and non-duct-fired operation. The boiler feed pumpsshall take suction from the LP</Text><Text id="14027" page="3">2.6 Shutoff Head: The head capacity characteristic curve shall be one that rises steadily from rated condition back to shutoff condition. Based upon the class/rating of the discharge piping, the rise-to-shutoff should be nominally 120 %, +/-5% of the curve-defining, rated condition oras limited by the established HRSG designconditions.</Text></Spec>